Everything the control system can command and measure, from the PLC program as deployed. This website is view-only today — controls arrive in a later phase; until then commands happen at the plant HMI. LIVE NOW streaming to this site · READY readable now, not yet collected · PARKED installed but offline · PROBATION needs attention before trusting.
Equipment
Tag
What we can do
How it runs
Data
Today
Blower 1 & 2
IT01-BA01/02
Start/stop · speed · Manual/Auto · fault reset
Lead-lag pair on blower-pressure PID (4.0 psi)
LIVE NOW
Auto, running
Storage Pump 1 & 2
IT03-PI01/02
Start/stop · speed · Manual/Auto · fault reset
Lead-lag pair on storage-pressure PID (7.0 psi)
LIVE NOW
Auto, running
Raw Water Pump 1 & 2
IT01-PI01/02
Start/stop · speed · Manual/Auto · fault reset
Lead-lag pair on raw-pressure PID
READY
Off — operator choice (sensor on probation)
Filtration Pump 1 & 2
GO01-PF01/02
Start/stop · speed · Manual/Auto · fault reset
Lead-lag pair on MBBR head-tank LEVEL PID (7.0 ft)
READY
Return Pump 1 & 2
GO01-PR01/02
Start/stop · speed · Manual/Auto · fault reset
Lead-lag pair on return-pressure PID
READY
Effluent HEX Pump
EF01-PX01
Start/stop · speed · Manual/Auto · fault reset
Own PID, run in Manual per design
READY
Intake Pump 1 & 2
IT02-PF01/02
On/off only (single-speed motors)
Own lead-lag pair
READY
Grow Out UV
GO01-UV01
On/off + shutdown-delay timer
Relay output
READY
Intake UV
IT02-UV01
On/off + shutdown-delay timer
Relay output
READY
Storage UV
IT03-UV01
On/off + shutdown-delay timer
Relay output
READY
Dose Pump
GO01-SI01
On/off AND speed 0–100 % with its own PID
Relay + analog speed signal
PARKED
Not in use since commissioning
Alarm Light + Buzzer
CP01-YA01/02
PLC-driven (UI test button possible)
Relay outputs
READY
VFD machines also accept speed-limit and ramp changes. “Data” = whether its readings reach this site yet.