RAS — PID Loops
Grow-out loop controllers
Connecting…—— ET🔔 Alarm Log
Bold / blue = live from the PLCGrey dotted = settings record (workbook), not read from the PLC yetView only — changes happen in WebVisu for now
LoopTagPV (live)Setpoint (live)Output (live)P GainI TimeD TimeOut MinOut Max
MBBR (Head Tank) Level
level loop — drives the filtration pumps
GO01-PF-PID………0.53.0 s0 s8 %100 %
Return PressureGO01-PR-PID………0.92.0 s0 s8 %100 %
Dosing (pH)
doses bicarb on demand
GO01-SI01-PID………1.24.0 s0 s0 %100 %
Effluent HEX
run in Manual per design
EF01-PX-PID………1.02.5 s0 s8 %100 %
Lead-lag — secondary start / stop speeds (record)
Motor pairSecondary StartSecondary Stop
Filtration A/B60 Hz41 Hz
Return A/B60 Hz40 Hz